Pump Specification Inlet diameter:200mm Outlet diameter:125mm Rating speed:2000rpm Rating capacity:100L/S Rating pressure: 0.5Mpa Efficiency: 83.1% NPSHr :8.9m Weight:274kg
Send InquiryChat NowFire Pump For Sale
Application
The fire pump set produced is in strict accordance with the national standard GB6245-2006 "fire pump performance requirements and test methods"and the NEPA20 standard of American Fire Protection Association.
Fire pump is suitable for the fire-fighting water supply and emergency water supply in storehouse, yard, airport, petroleum and chemical industry, power plant, liquefied gas,textile, oil ship.



Pump Features and Function
As the auto-control group, a separate diesel engine auto-control cabinet (programmable) carries out the system's automatic starting, putting into use, auto-switching( the motor pump group is switched to the diesel engine pump one or the diesel engine pump group to another group), auto- protection(warning and stopping protection for the diesel engine'sover-speed, lower oil pressure, high water temperature, three times failures of starting, low voltage of accumulator etc.) etc. functions and also can be connected to fire-fighting centers of users or the autowarning device of fire to get a remote monitoring.
To ensure the group to normally working an environment of below 5°, it can be fitted with and AC220V cooling-water preheater.
Working Time
The oil tank used for the diesel engine of a power below 200kW can be directly mounted on the unit while the one for the diesel engine of a power over 200kW can bes eparated from the unit. The following listed oil tank's volumes can ensurethe diesel engine fire-fighting pump groups of different powers to normally work under the rated working condition for 8 hours.

Pump Maintenance
1.According to the requirement in the fire-fighting standard,the unit must run once at least every 15-day with time not less than15minutes so as make sure of it in a good status at any time.
2. Every time to start the fire-fighting pump, it should be done to check if the shaft seal is normal and if it needs to be adjusted or replaced.
3. Periodically lubricate the bearing with grease.
4. Completely drain the water inside of the pum p out in case of
a long time stop of the opump to prevent the pump casing etc Parts from being frozen to result in split due to extra low amb-ient temperature .
5. according to the provision for the maintenance of the diesel en-gine, daily maintenance should be kept for it by checking if the cooling water quantity, engine oil quaqntity, the accumulator's voltage, oil-pressure meter, thermometer, speed-ometer and other control devices are normal.

Hot Tags: Fire Pump For Sale, China, manufacturers, suppliers, distributor, wholesale, price, buy, for sale